Rack unit

22 Mar.,2024

 

Unit of measure for electronic equipment

Rack with sample component sizes including an A/V half-rack unit A typical section of rack rail, showing rack unit distribution

A rack unit (abbreviated U or RU) is a unit of measure defined as 1+3⁄4 inches (44.45 mm).[1][2] It is most frequently used as a measurement of the overall height of 19-inch and 23-inch rack frames, as well as the height of equipment that mounts in these frames, whereby the height of the frame or equipment is expressed as multiples of rack units. For example, a typical full-size rack cage is 42U high, while equipment is typically 1U, 2U, 3U, or 4U high.

Definition

[

edit

]

The rack unit size is based on a standard rack specification as defined in EIA-310. The Eurocard specifies a standard rack unit as the unit of height; it also defines a similar unit, horizontal pitch (HP), used to measure the width of rack-mounted equipment. The standard was adopted worldwide as IEC 60297 Mechanical structures for electronic equipment – Dimensions of mechanical structures of the 482.6 mm (19 in) series, and defines the sizes for rack, subrack (a shelf-like chassis in which cards can be inserted), and the pitch of printed circuit boards/cards providing physical compatibility of technological equipment, typically in telecommunications.[citation needed]

While a rack unit is defined as 1+3⁄4 inches (44.45 mm), a front panel or filler panel in a rack is not an exact multiple of this height. To allow space between adjacent rack-mounted components, a panel is 1⁄32 inches (0.03125 in or 0.794 mm) less in height than the full number of rack units would imply. Thus, a 1U front panel would be 123⁄32 inches (1.71875 in or 43.66 mm) tall. If n is number of rack units, the ideal formula for panel height is h = (1.75n − 0.031) for calculating in inches, and h = (44.45n − 0.794) for calculating in millimetres. Manufacturing allows for dimensions with less precision.

The 19-inch rack format with rack units of 1.75 inches (44.45 mm) was established as a standard by AT&T around 1922 in order to reduce the space required for repeater and termination equipment in a telephone company central office.[3]

Configurations

[

edit

]

A typical full-size rack is 42U,[4] which means it holds just over 6 feet (180 cm) of equipment, and a typical "half-height" rack is 18–22U, which is around 3 feet (91 cm) high.

Conversion table Rack unit inches mm 1U 1.75 44.45 2U 3.5 88.9 3U 5.25 133.35 4U 7 177.8 5U 8.75 222.25 6U 10.5 266.7 7U 12.25 311.15 8U 14 355.6 9U 15.75 400.05 10U 17.5 444.5 11U 19.25 488.95 12U 21 533.4 13U 22.75 577.85 14U 24.5 622.3 15U 26.25 666.75 16U 28 711.2 17U 29.75 755.65 18U 31.5 800.1 19U 33.25 844.55 20U 35 889 21U 36.75 933.45 22U 38.5 977.9 23U 40.25 1022.35 24U 42 1066.8 25U 43.75 1111.25 26U 45.5 1155.7 27U 47.25 1200.15 28U 49 1244.6 29U 50.75 1289.05 30U 52.5 1333.5 31U 54.25 1377.95 32U 56 1422.4 33U 57.75 1466.85 34U 59.5 1511.3 35U 61.25 1555.75 36U 63 1600.2 37U 64.75 1644.65 38U 66.5 1689.1 39U 68.25 1733.55 40U 70 1778 41U 71.75 1822.45 42U 73.5 1866.9

Mounting holes

[

edit

]

The mounting-hole distance (as shown to the right) differs for 19-inch racks and 23-inch racks: 19-inch racks use uneven spacings (as shown to the right) while 23-inch racks use evenly spaced mounting holes. Although it is called a 19-inch rack unit, the actual mounting dimensions of a 19-inch rack unit are 185⁄16 inches (18.3125 in or 465.1 mm)[5] wide, center to center.

Rack units are universally the same, but the type of thread[6] can vary depending on the rack. Mounting rails can be No. 10-32 tapped (Unified Thread Standard), No. 12-24 tapped, metric M6 threaded or universal square holes. Universal square holes are becoming the most common as these allow the insertion of replaceable cage nuts for the type of thread needed.[citation needed] This prevents stripping of the threading on the rails and allows for more flexibility.

Half-rack configurations

[

edit

]

Whereas there is no formal specification for "half rack", the term half-rack can have different separate meanings: It can describe equipment that fits in a certain number of rack units, but occupy only half the width of a 19-inch rack (9.5 inches (241.30 mm)). These are commonly used when a piece of equipment does not require full rack width, but may require more than 1U of height.[citation needed] For example, a "4U half-rack" DVCAM deck occupies 4U (7 in) height × 9.5 in width, and in theory, two 4U half-rack decks could be mounted side by side and occupy the 4U space. It can also describe a unit that is 1U high and half the depth of a 4-post rack (such as a network switch, router, KVM switch, or server), such that two units can be mounted in 1U of space (one mounted at the front of the rack and one at the rear). When used to describe the rack enclosure itself, the term "half-rack" typically means a rack enclosure that is half the height (22U tall). There is also a "half rack width" size being used in IT applications where a device conforms to a smaller than 9.5-inch width so that these "half rack width" appliances may be used in a chassis system that fits the traditional 19-inch rack space, but allows for these 8.4-inch-wide "half rack width" appliances to be inserted and removed easily without tools or the need to remove adjacent hardware. This "half rack width" concept is popular in applications where IT equipment is being used by military who are unable to use traditional 1U full-depth IT appliances due to their large size.

See also

[

edit

]

References

[

edit

]